Street Light Control System PLC Version
How to Configure Concentrator of the Street Light Control System PLC Version
You can either use the GUI utility: http://www.linksprite.com/download/showdownload.php?id=62&lang=en
Or telnet to the concentrator. For the telnet username and password, please email support@linksprite.com
Under /flash, there is a file named: system.conf
# Configuration for application
[VERSION]
VCODE=B2
V1=10
V2=1
V3=26
VER=V2008.120.020
ISSUEDATE=2008-12-02
[CLIENT]
BakIPFixed=0
rj45IPFixed=0
gprsIPFixed=0
# 0=NONE, 1=AUTO, 2=MANUAL
ConnectType=1
# 1=RJ45, 2=GPRS
Connection=1
# GPRS Configure
GprsSIP=mail.linksprite.com
GprsSPort=4022
# RJ45 Configure
Rj45SIP=192.168.1.106
Rj45SPort=4022
RConnTimesMax=0
ConnectEnabled=1
BakDomainEn=40
BakDomain=mail.linksprite.com
BakSPort=4082
[RS485]
DEVNAME=/dev/rs4850
# SET TO RLT/PD194E/AMMETER...
AMR485_TYPE=PD194E
[CC]
CC_DETAILED_MSG=1
CC_HEARTBEAT_MAX=10
CC_RXIDLETIME_MAX=5
CC_RXIDLE2TIME_MAX=60
CC_RXIDLETIME_INTERVAL=30
CC_RESETCC_FIRST_DELAY=60
DEVNAME=/dev/ttyS1
# SET TO BCAST/BCAST2
BroadcastType=0
LineCheckFirstTime=0
COMDEVNAME=/dev/tts/4
# Controller Version: 0=CC polling all the nodes, 1=ARM polling all the nodes using flooding, 2=ARM Net build
CCModel=1
CCManufactory=0
ResetEnable=1
[LOCALSERVER]
PORT=99
CLIENT_MAX=4
[SYSTEM]
ROOTDIR=/var/tmp
WATCHDOGTMO=255
autoSMSSyncTimeCycle=2880
autoSaveTimeCycle=10
autoLogHeartbeatCycle=60
allowUseLCD=1
[TASK]
MAX_TASKLIST=400
[MOBILE]
SMSC_ADDR=10086
DEVNAME=/dev/ttyS2
# 1.4800,2.9600,3.19200,4.38400,5.57600,6.115200
BAUDRATE=6
GprsEnabled=1
GprsResetDown=10
GprsResetOvertime=8
ApnEnabled=0
ApnDomain=wap.cingular
ApnNeedAuth=0
ApnUser=user
ApnPasswd=1234
[LOCAL]
IPADDR=C0A80112
NETMASK=FFFFFF00
GATEWAY=C0A80101
dnsEnable=0
DNS1=00000000
DNS2=00000000
[ALARMCHECK]
cycle=60
interval=0
timeout=1000
timeoutMaxTimes=3
LineCheckFirstTime=0
achkMode=255
grpNum=0
[LINE]
LineStatus=0
We can use vi to edit the IPADDR.
Next:No Information